Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
Digital Monitoring Products
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
21.6 XR5SL Connection to FACP
1
2
3
4
5
6
7
8
Normally Open
Common
Normally Closed
3.3k
Normally Open
Common
Normally Closed
Normally Open
Common
Normally Closed
Positive 12/24 VDC Auxiliary Ouput
Negative 12/24 VDC Auxiliary Ouput
3.3k
3.3k
ZONE 5
AC
1
234
78
10 11 12
13
14
15
16
AC B+ B–
9
RED
YEL GRN
BLK
Z1B–
Z2 –
Z2+
U21
1
2
3
4
J12
Z1A–
Z1B+
Z1A+
MODEL XR5
MAIN
BACKUP
PANEL
RESET
EPROM Socket
J11
N/C COM N/O N/C COM N/O
J4
J5
Telephone Connections
ZONE 1
5
6
BELL
SMK
OUTPUT 1
OUTPUT 2
SILENCE/RESET
PUSH FOR ONE SECOND
17
18
Z3 –
Z3+
19
20
Z4 –
Z4+
21
22
Z5 –
Z5+
3.3k
ZONE 4
3.3k
ZONE 3
{
Form C alarm contacts
activate on General
Alarm.
S
= Supervised Circuit
S
S
S
S
S S S S
S S S
S
ZONE 2
Form C trouble contacts
activate on General Trouble.
General Trouble must not
be used to indicate AC
power fail unless it can be
delayed 6 to 12 hours.
Form C or A contacts
activate on Supervisory
condition.
{
{
AC Mode Wiring
When the XR5SL is used in the AC mode, the DMP
Model 320 Transformer must be connected to the
same branch circuit as the FACP. An AC power fail
can then be delayed 6 to 12 hours by the XR5SL
programming. See section 5.4 of the XR5SL
Programming Guide (LT-0312).
The FACP must not indicate AC fail to the XR5SL.
Use Fire-Lite Models MS9200 or MS5012.
3.3k
Normally Open
Common
Normally Closed
{
Form C contacts activate on
AC power fail. Use on
XR5SL in DC mode only.
Must delay AC power fail 6
to 12 hours.
S S
DMP Model 320
Transformer
AC Mode
Optional DC Mode
120 VAC
60Hz
350mA
Main Fire Alarm
Control Panel (FACP)
DC Mode Wiring
When the XR5SL is used in the DC mode, the FACP
must indicate AC power fail on an independant relay
output. This output must delay the AC power fail 6
to 12 hours. Use EST Model IRC-3 or Federal Signal
3000, 5000, or 5000E.