Page 9
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
Keypad Data Bus
9.1 Description
Terminals 7, 8, 9, and 10 of the XR5FC and XR5SL panels provide the keypad data bus to which you can
connect Model 692F LED keypads as well as two alphanumeric Security Command keypads.
9.2 Terminal 7 - RED
Terminal 7 provides 12 VDC keypad power for Security Command keypads. You can also connect 12 VDC
auxiliary devices to terminal 7. The ground reference for terminal 7 is terminal 10. The maximum output is rated
at 500mA on the XR5FC and XR5SL panels. All auxiliary devices totalled together must not exceed the panel's
maximum current rating.
9.3 Terminal 8 - YELLOW
Data receive from keypads.
9.4 Terminal 9 - GREEN
Data transmit to keypads.
9.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for keypads and any auxiliary devices being powered by terminal 7.
Class A (Style D) Fire Zone
10.1 Description
Terminals 11 to 14 are the panel's Class A (Style D) fire zone. This zone is suitable for connecting waterflow
devices, heat detectors, and other non-powered fire devices. For programming purposes, this is zone number 1.
The zone is rated for 1.66mA at 5.0 VDC.
The zone configuration on terminals 11 to 14 are described below.
Terminal Function Terminal Function
11 Zone 1 voltage sensing 12 Negative for terminal 11
13 Zone 1 voltage sensing 14 Negative for terminal 13
The voltage sensing terminal measures the voltage flowing through the circuit to the zone's negative terminal.
Dry contact sensing devices can be used only in parallel (normally-open) with zone 1. There are no End of Line
resistors on a Class A (Style D) zone.
Class B (Style A) Fire Zones
11.1 Description
Terminals 15 to 22 are the Class B (Style A) fire zones on the XR5FC and XR5SL panels. These zones are
suitable for connecting powered or non-powered fire devices. For programming purposes, these zones are
designated 2 to 5. The zone configurations on terminals 15 to 22 are described below:
Terminal Function Terminal Function
15 Zone 2 voltage sensing 16 Zone 2 negative
17 Zone 3 voltage sensing 18 Zone 3 negative
19 Zone 4 voltage sensing 20 Zone 4 negative
21 Zone 5 voltage sensing 22 Zone 5 negative
11.2 Operational parameters
The Class B (Style A) zones on the XR5FC and XR5SL panels can detect three conditions: open, normal, and
short. Each zone terminates with a Model 309, 3.3k Ω EOL resistor (provided with the panel) and is rated for
53mA at 12 VDC.
The UL compatibility identifier for use with 2-wire smoke detectors is: A.