Page 11
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
Telephone RJ Connector
14.1 Description
Connect the panel to the public telephone network by installing DMP 356 RJ Cables between the panel's J4
(MAIN) and J5 (BACKUP) connectors and the RJ31X or RJ38X phone jacks.
14.2 FCC registration
The XR5FC and XR5SL panels comply with FCC part 68 and are registered with the FCC.
Registration number: CCK USA - 18660 - AL - R
Ringer Equivalence: 1.1B
14.3 Notification
Registered terminal equipment must not be repaired by the user. In case of trouble, the device must be
immediately unplugged from the telephone jack. The factory warranty provides for repairs. Registered terminal
equipment may not be used on party lines or in connection with coin telephones. Notification must be given to
the telephone company of:
a. The particular line(s) the service is connected to
b. The FCC registration number
c. The ringer equivalence
d. The make, model, and serial number of the device
Reset Jumpers J9
15.1 Description
There are two reset jumpers located at the top right of the panel's circuit board labeled RESET. Momentarily
shorting these jumpers allows you to reset the microprocessor of the XR5FC and XR5SL panels allowing you to
enter the internal Programmer.
You can reset the panel while the system is operational (for example, during a service call) without powering
down the system.
After resetting the panel for programming, you must begin within 30 minutes. If you wait longer than 30 minutes,
you'll have to reset the panel again.
Silence/Reset button
16.1 Silence/Reset button
The XR5FC and XR5SL panels each contain a mechanical push button located on the top center of the printed
circuit board that allows authorized users to silence alarm bells or sirens and reset latched detection devices.
After pressing the button, the panel silences the Bell output (XR5FC terminal 5) and momentarily drops power to
the auxiliary output (XR5FC terminal 6), the 377 Trouble Annunciator Module, and zones 2 to 5 (both panels).
Additionally, any Fire or Supervisory event displays at the keypads are also cleared. A 2-pin reset header is also
provided for use with keyswitches.
Dual Phone Line Connectors
17.1 Description
The XR5FC and XR5SL panels contain built-in dual phone line capability that allows the panel to monitor two
phone lines, indicate a phone line failure, and switch to the alternate phone line to communicate alarm and
system reports to a central station.
Before sending a report, the panel verifies whether the main phone line is working. If not, the panel sends the
report over the backup phone line. An integrated phone line monitor circuit continually tests the phone lines and
indicates a trouble condition on the line after 90 seconds. If the phone line restores and is good for 90 seconds,
the panel ends the phone line trouble indication.