Page 10
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
11.3 Zone response time
A condition must be present on the zone for at least
500 milliseconds before it is detected by the XR5FC
and XR5SL panels. Ensure detection devices used on
the zones are rated for use with this delay.
11.4 Compatible 2-wire smoke detectors
The table to the right lists those detectors meeting the
compatibility requirements for use with the Class B
(Stlyle A) zones on the XR5FC and XR5SL fire
panels.
Do not mix detectors from different manufacturers on
the same zone.
Form C Relay Outputs
12.1 Description
The XR5FC and XR5SL panels can provide two auxiliary Form C (SPDT) relays when equipped with DMP
Model 305 Plug-in Relays in sockets OUTPUT 1 and OUTPUT 2. Each relay is rated for 1 Amp at 30 VDC.
Each output provides one Common, one Normally Open, and one Normally Closed terminal. Field wiring for the
Form C relays connects to the 6-position terminal strip on the lower right corner of the XR5FC and XR5SL
boards.
The Form C relays can be operated by any of the functions listed below:
1) Activation by a zone condition
2) Communication Failure
3) Fire alarm or Fire trouble
Annunciator Outputs
13.1 Description
The XR5FC and XR5SL panels provide four open collector annunciator outputs that can be programmed to
indicate the activity of the panel's zones or conditions occurring on the system. Open collector outputs do not
provide a voltage but instead switch to ground voltage from another source. Each annunciator output is
rated for 50mA at 30 VDC resistive.
Form C and Annunciator outputs operate together:
The Form C outputs 1 and 2 are internally connected to
the Annunciator outputs 1 and 2. Any options assigned to Output 1 or 2 in the panel's Output Options
programming applies to both outputs. While the Form C outputs each require a Model 305 Plug-in Relay, the
annunciator outputs will work without the relays.
The Annunciator outputs can respond to any of the conditions listed below:
1) Activation by zone condition
2) Communication failure
3) Fire Alarm or Fire Trouble
13.2 Harness wiring
The Annunciator outputs are accessible by installing the DMP 300 Harness on the 4-pin header labeled J12.
The output locations are shown below:
Output Color Wire
1 Red 1
2 Yellow 2
3 Green 3
4 Black 4
Devices connected to the outputs must be located within the same room as the XR5FC and XR5SL panels.
Figure 6: Compatible 2-wire smoke detectors
ekaMledoMrotceteD
DI
esaBesaB
DI
fo#
srotceteD
smetsySnoitceteD282SDB enoNA/N01
smetsySnoitceteDHT282SDB enoNA/N01
smetsySnoitceteD052SDB LW2BM,W2BMA01
smetsySnoitceteDHT052SDB LW2BM,W2BMA01
smetsySnoitceteDDH052SDB LW2BM,W2BMA01
LSE/lortneSTA924A90SenoNA/N21
ikihcoH538-KLS5-DHN002-BSH,002-BSH55-BH7
ikihcoHH538-KLS5-DHN002-BSH,002-BSH55-BH7
ikihcoH21-KLS4-DHN1-21-BSH,1-21-BSH08BH02
Comentários a estes Manuais