Page 13
Installation
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR5FC/XR5SL Installation Guide
21.1 Multiple 866 Notification Circuit Modules
ZONE 2
AC
1
234
78
10 11 12
13
14
15
16
AC B+ B–
9
RED
YEL GRN
BLK
Z1B–
Z2 –
Z2+
3.3k
U21
1
2
3
4
J12
Z1A–
Z1B+
Z1A+
MODEL XR5
MAIN
BACKUP
EPROM Socket
J11
N/C COM N/O N/C COM N/O
J4
J5
ZONE 1
S
S
5
6
BELL
SMK
OUTPUT 1
OUTPUT 2
SILENCE/RESET
PUSH FOR ONE SECOND
17
18
Z3 –
Z3+
19
20
Z4 –
Z4+
21
22
Z5 –
Z5+
W
W
3.3k
ZONE 4
3.3k
ZONE 3
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
AUXILIARY
POWER
SUPPLY
24 VDC 5 Amp
Maximum
Power Supply
Trouble Contacts
N/C
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
Notification Circuit Module
DMP Model 866
37mA at 12 VDC
The Auxiliary Power Supply and Indicating
Circuit Module trouble contact zone must
be programmed as a Supervisory Type zone.
NOTE: If an auxiliary supply is not used,
terminals 3 and 4 on the 866 Notification
Circuit Module can be jumpered together
to supply bell power from the XR5F panel.
A maximum of 1.5 Amps at 12 VDC is available
from terminal 5 of the XR5F.
Auxiliary power supply must be regulated
UL listed for Fire Protection Signaling Service.
Power supplies must have battery backup.
UL Listed, Polarized
Indicating Devices.
10k EOL Resistor
DMP Model 308
1
2
3
4
5
6
7
8
Auxiliary Power
Ground
Alarm Input
Bell Power Input
Bell Output +
Bell Output -
Bell Trouble
Bell Trouble
AUXILIARY
POWER
SUPPLY
Power Supply
Trouble Contacts
N/C
24 VDC 5 Amp
Maximum
3.3k
To additional eleven 866 Notification Circuit
Modules. Up to a maximum of thirteen 866
modules on the XR5 panels. Modules must
be installed in a Model 340FC, 340SL, 349, or
350 enclosure connected by no more than 20
feet of conduit.
Each 866 Notification Circuit Module
in alarm draws up to 35mA from its
terminal 3 alarm input.
Notification Circuit Module
DMP Model 866
37mA at 12 VDC
PANEL
RESET
S
= Supervised Circuit
S
SS S S
S S S S S S S S
S S
S
S
S